Power Quality Analysis & Project Scope
At Fourth Phase Electrics we specialise in Power Quality and Power Factor Correction.
In another project led to us by the team at Fuseco Power Solutions, we were recommended and engaged to supply and install our power quality analyser and provide data on the facilities consumption.
After a weeks worth of data had been analysed, we discovered that Food Plastics, were running at nearly full capacity on their 3200a supply, with a poor power factor and heavy phase imbalance.
It was calculated that they needed a 500kVar Static Var Generator to bring their power factor from around .8 lagging, up to .96, and achieve significantly better phase balancing, to within a percent or so.
SVG Installation & Shutdown Management
We installed the SVG unit in a neat, out of the way position as per our clients request. The shutdown was completed after hours and went incredibly safely, and smoothly. As we provided significant notice, they were also able to schedule in the servicing of their ACB’s – another nod in the benefits of engaging a company who prides itself on clear communication and meticulous planning.
Performance Improvements & Client Outcomes
The outcome of this install means that the clients sub station kiosk has far less burden on it, they are at much less risk of overloading and potentially tripping their supply capacity control, they have a significant saving on their energy bill due to lower kVar tariffs, and the many millions of dollars worth of high end blow moulding equipment will have a longer lifespan within the facility itself.
Overall this was a fantastic solution for Food Plastics, and another testament to a quality, data driven approach to find the correct outcome for our client.